Performance Analysis of a 220 V DC Lead-Acid Battery Using the Dummy Load (Torkel 840) Method in The Electrical System of a Steam Power Plant 2x 100 MW
DOI:
https://doi.org/10.25077/aijaset.v6i1.317Abstract
Battery performance can be affected by operational disturbances such as overcharging and deep discharging, which may lead to voltage instability, temperature rise, and accelerated degradation. This study analyzes the effect of discharge current on the voltage and temperature characteristics of a lead-acid battery in a 220 V DC LAA system using a dummy load method. The experimental test was conducted using a Torkel 840 battery discharge tester with a constant discharge current of 25 A for a duration of 10 hours. Parameters including total battery voltage, average cell voltage, battery temperature, and electrolyte specific gravity were measured periodically during the discharge process. The minimum allowable battery voltage was determined based on manufacturer specifications to ensure safe operation. The results indicate that the battery voltage decreased gradually and remained above the minimum allowable limit of 187.2 V, demonstrating stable voltage performance under constant load conditions. Battery temperature increased moderately from 22.36 °C to 25.93 °C and remained within the recommended operating range. The electrolyte specific gravity showed a consistent decrease corresponding to normal electrochemical behaviour. These results confirm that the tested lead-acid battery is suitable for reliable operation as a DC backup power source in power plant applications.
References
[1] C. K. Das, O. Bass, G. Kothapalli, T. S. Mahmoud, and D. Habibi, “Overview of energy storage systems in distribution networks: Placement , sizing , operation , and power quality,” Renew. Sustain. Energy Rev., vol. 91, no. March 2018, pp. 1205–1230, 2019, doi: 10.1016/j.rser.2018.03.068.
[2] G. J. May, A. Davidson, and B. Monahov, “Lead batteries for utility energy storage: A review,” J. Energy Storage, vol. 15, pp. 145–157, 2018, doi: 10.1016/j.est.2017.11.008.
[3] B. Mosallanejad and M. Akrami, “Recent advances on electrolyte additives used in lead-acid batteries to enhance their electrochemical performances,” J. Energy Storage, vol. 97, no. PA, p. 112738, 2024, doi: 10.1016/j.est.2024.112738.
[4] A. P. Baterai, “Analisis Penggunaan Baterai Lead Acid dan Lithium Ion dengan Sumber Solar Panel,” vol. 11, no. 2, pp. 392–407, 2023.
[5] C. Li, X. Liu, C. Wang, L. Ye, and T. Wu, “Case Studies in Thermal Engineering Electrochemical-thermal behaviors of retired power lithium-ion batteries during high-temperature and overcharge / over-discharge cycles,” Case Stud. Therm. Eng., vol. 61, no. July, p. 104898, 2024, doi: 10.1016/j.csite.2024.104898.
[6] W. E. Gent et al., “Persistent State-of-Charge Heterogeneity in Relaxed , Particles,” pp. 1–8, 2016, doi: 10.1002/adma.201601273.
[7] L. Qian, Y. Yi, W. Zhang, C. Fu, C. Xia, and T. Ma, “Revealing the Impact of High Current Overcharge / Overdischarge on the Thermal Safety of Degraded Li-Ion Batteries,” vol. 2023, 2023, doi: 10.1155/2023/8571535.
[8] A. Al-hinai, H. Alyammahi, and H. Haes, “Coordinated intelligent frequency control incorporating battery energy storage system , minimum variable contribution of demand response , and variable load damping coefficient in isolated power systems,” Energy Reports, vol. 7, pp. 8030–8041, 2021, doi: 10.1016/j.egyr.2021.07.072.
[9] F. Kokalj and P. Kitak, “Lead-Acid Battery Sizing for a DC Auxiliary System in a Substation by the Optimization Method,” 2019.
[10] A. Culcasi et al., “Improving efficiency and discharge power of acid-base flow battery via a bi-objective optimisation,” J. Energy Storage, vol. 66, no. March, p. 107429, 2023, doi: 10.1016/j.est.2023.107429.
[11] S. A. Hasib et al., “A Comprehensive Review of Available Battery Datasets , RUL Prediction Approaches , and Advanced Battery Management,” IEEE Access, vol. 9, pp. 86166–86193, 2021, doi: 10.1109/ACCESS.2021.3089032.
[12] Z. Almutairi and H. A. Bheyan, “Reducing Lithium-Ion Battery Testing Costs Through Strategic Sample Optimization,” pp. 1–26, 2025.
[13] J. Zhao, X. Feng, M. Tran, M. Fowler, M. Ouyang, and A. F. Burke, “Battery safety: Fault diagnosis from laboratory to real world,” J. Power Sources, vol. 598, no. December 2023, p. 234111, 2024, doi: 10.1016/j.jpowsour.2024.234111.
[14] “Battery testing guide „ Why backup batteries are needed „ Battery types „ Failure modess „ Maintenance philosophies „ Practical battery testing „ Frequently asked questions „ Megger products overview Contents”.
[15] S. Applications, IEEE Standards, vol. 2002. 2003.
Downloads
Published
How to Cite
Issue
Section
License
Copyright (c) 2026 Witri Onanda, Muhardika, Resti Savira, Akbar Abadi, Anisa Amir

This work is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.