Effect of humidity and contaminants on dry band formation in Outdoor Distribution Current Transformer 20 kV

Authors

  • Satia Zaputra Kebangsaan University of Bandung

DOI:

https://doi.org/10.25077/aijaset.v1i02.23

Abstract

This study reports the effect of humidity and pollutants on the formation of dry band phenomena on the insulation surface of an outdoor 20 kV distribution current transformer. From the results of measurements at high humidity 95% and high conductivity 36 mS/cm at a working voltage of 2-20kV test there is a change in the curve of increasing the value of the leakage current which is very volatile. Wet layer of impurity will cause a drastic decrease in surface resistance resulting in a large increase in leakage current. At a high conductivity of 36 mS/cm, the results of the measurement of surface resistance at low humidity of 55% worth 30.2 giga ohms decreased to 2.1 giga ohms at high humidity of 95%. While the value of the leakage current curve is very fluctuating from the value of 206 - 678 A at high conductivity with heavy pollutants. This information confirms the hypothesis that the boundary region of the two air-solid dielectrics of the epoxy resin causes surface discharge problems in dry band formation due to an increase in the non-uniform local electric field in the impurity layer adhering to the surface of the distribution current transformer.

Keywords : leakage current, dry band, surface discharge, contaminants

References

S. Zaputra, "Leakage current and partial discharge characteristics of epoxy resin material of distribution current transformer in salt fog pollutant condition," 2017 International Conference on High Voltage Engineering and Power Systems (ICHVEPS), 2017, pp. 508-513.

M. M. Hussain, S. Farokhi, S. G. McMeekin and M. Farzaneh, "Dry band formation on HV insulators polluted with different salt mixtures," 2015 IEEE Conference on Electrical Insulation and Dielectric Phenomena (CEIDP), 2015, pp. 201-204

Suwarno and S. Ardianto, "Characteristics of leakage current and flashover on epoxy resin insulator," 2014 IEEE Workshop on Electronics, Computer and Applications, 2014, pp. 754-757.

N. Anami et al., "Evaluation of dry band arc on the polymeric insulator using differential technique and distortion factor of leakage current," 2003 Annual Report Conference on Electrical Insulation and Dielectric Phenomena, 2003, pp. 414-417

N. Anami et al., "Proposal of separate technique using differential value of leakage current," Annual Report Conference on Electrical Insulation and Dielectric Phenomena, 2002, pp. 339-342.

H. Homma, T. Kuroyagi, T. Takahashi, S. Ohtsuka and M. Hikita, "Algorithm for determining the surface leakage current on polymer insulating materials based on current waveform distortion," Annual Report Conference on Electrical Insulation and Dielectric Phenomena, 2002, pp. 676-679.

Downloads

Published

2021-11-18

How to Cite

Zaputra, S. (2021). Effect of humidity and contaminants on dry band formation in Outdoor Distribution Current Transformer 20 kV. Andalasian International Journal of Applied Science, Engineering and Technology, 1(02), 84-89. https://doi.org/10.25077/aijaset.v1i02.23